In many applications of perforated plate, the estimated energy loss or
pressure loss through perforated plates is one of the design considerations.
The following pressure loss information was developed from a laboratory
air flow system. The laboratory system maintained a non-swirling flow impacting
perpendicularly on the sample. Various perforated thin gage plates were
inserted into a uniform velocity air flow stream. Pressure loss for ambient
air flow was then measured at a series of velocities and reported as inches
of water column loss for each flow. This data therefore presents the best
flow condition value of loss. Pressure loss can be estimated beyond the
range of the data on the basis of the ratio of the anticipated velocity
to the highest tabulated velocity. This ratio squared multiplied by the
tabulated pressure loss can be used to approximate the higher velocity
loss. Click on a link below. |